NAV IP Access controller
111
whenacardisswipedatanydooratwhichitdoesnothavetherighttopass.Thecontroller
generatesalarmoutput(s)accordingtothesettinginthe“InvalidDoor”column.
Invalid Time: Each card belongs to an access group. For each group, the system can assign
accessrights
tocertaindoorsforcertaintimezones.Aninvalidtimeeventwillbegeneratedif
acardisswipedduringatimeperiodinwhichitdoesnothavetherighttopass.Thecontroller
generatesalarmoutput(s)accordingtothesettinginthe“InvalidTime”column.
APBFail:
IfthecardAPBpropertyisenabled,anddoorbehaviorunderAPBissetto“unlock”.
Acardholderwillbeabletoenter/exitanydoorsbyswipingthecard. The system generates
an APB fail event if an APB event is triggered. The controller generates alarm output(s)
accordingtothesetting
inthe“APBFail”column.
Card PIN Fail: A card PIN fail event is generated when a PIN‐enabled card is presented at a
reader and an incorrect PIN is entered three times consecutively. The controller generates
alarmoutput(s)accordingtothesettinginthe“CardPINFail”column.
DoorForcedOpen:Adoorforcedopeneventisgeneratedwhenthedoorsensorindicatesto
the controller that a door is opened, but no legitimate card has been presented and a
Request‐to‐Exit button has not been pressed. The controller generates alarm output(s)
accordingtothesettingin
the“DoorForcedOpen”.Inpractice,adoorforcedopeneventwill
begeneratedifadooriskickedopen.
Door endures Open:A doorenduresopeneventisgeneratedifa cardholderentersendures
PINtounlockadoorwhenunderendures.Thecontrollergeneratesalarmoutput(s)according
tothesettinginthe“DoorenduresOpen”.
Door Held Open/Overtime: the system keeps tracking of the door status when a card is
presentedtoareaderorRequest‐to‐Exitbuttonispressed.Adoorheldopen/overtimeevent
occurs when a door is held open for longer than the
allowed door held open time. The
controllergeneratesalarmoutput(s)accordingtothesettinginthe“DoorHeldOpen”column.
ReaderLost:Areaderlosteventisgeneratedwhenthecontrollerdetectsthatthecardreader
appearstohavebeendisconnectedfromthesystem.Thecontrollergeneratesalarmoutput(s)
accordingtothesettinginthe“ReaderLost”column.
Panic door: Whenan accessdeniedappearsand request opendidnot implement, however,
door magnetic sensor is displayed the door have been opened, it will lead a “panic door”
event. The controller generates alarm output(s) accordingtothe setting in
the “Panic Door”
column.
Steps:
1) Clickthe“AlarmAction”tabpage
2) Selectanalarmtobesetinalarmlist.
3) Inthecorresponding,clickthepositiontoshowdrop‐downmenuofalarmoutput,
selecttheoutputvalue:R,Y,N.
4) Clickthe“Save”buttontosaveyourchanges.
12.1.5.5 Alarm Time
Onthealarmtimesettingpage,userscansetthealarmtimeforthespecifiedcontroller.